Reference Manual
00809-0100-4530, Rev BA
July 2009
6-5
Rosemount 5300 Series
Using DeltaV
1. Click the right mouse button on the transmitter icon and choose the
Properties option.
2. Select the Transducer1100 block.
3. Select the LCD tab.
Figure 6-4. The Transducer
1100 block lets you specify
variables for the 5300 Display
Panel.
4. Choose the variables you want to appear on the Display Panel and the
corresponding measurement units.
You can specify the same measurement units as selected in the Product
Values tab and in the Interface Values tab by choosing the Auto option
for the LCD Unit.
The LCD will alternate between the selected display parameters.
The available LCD parameters are listed in Table 6-1 on page 6-6.
5. Click the OK button to save the LCD settings in the transmitter database.